PLX51-PBM PROFIBUS DP Master/Slave to EtherNet/IP™, Modbus TCP/IP®, or Modbus® Serial Gateway
PLX51-PBM

The PLX51-PBM gateway provides connectivity to EtherNet/IP™, Modbus TCP/IP®, or Modbus® Serial networks for PROFIBUS DP networks by operating as either a Master or Slave device on the PROFIBUS DP network.

For easy integration to a Rockwell Automation Controller, the gateway and configuration software create dynamic AOI’s based on the user configuration to add logical tag names to the PLC project file. Thus, reducing the overall programming time for EtherNet/IP applications.

For configuration of Modbus TCP/IP or Modbus Serial Networks, the module will automatically map PROFIBUS DP data points to registers on a Modbus network.

With advanced tools such as PROFIBUS device discovery and a built-in PROFIBUS DP packet capture utility, PROFIBUS DP network commissioning time can be greatly reduced.

Dual Ethernet ports of the module can support either DLR (Device Level Ring) topology, or can be used as an embedded switch for flexible installation options.

With support for up to 1536 bytes of Input and Output data, and up to 4 EtherNet/IP connections to the processor, this module provides performance and data throughput back to the processor for even the most demanding of PROFIBUS applications.

When used as a PROFIBUS DP slave, the module can operate as 1 to 10 slaves, providing up to 1536 bytes of Input and Output Cyclic I/O data between EtherNet/IP, Modbus TCP/IP, or Modbus Serial devices and a PROFIBUS DP master.

Specifications

EtherNet/IP™ Server

As an EtherNet/IP server, the gateway can support up to 4 Class 1 I/O connections back to a Controller on an EtherNet/IP network. Additionally, the server can respond to Class 3 messages from an EtherNet/IP client for the transfer of Status and PROFIBUS DP data.

Modbus TCP/IP

On a Modbus TCP/IP network, the module will operate as either a Modbus TCP/IP Client or Server device.

As a Modbus TCP/IP client the module can be configured to automatically read/write all PROFIBUS DP data with a slave device for easy setup and configuration, or the Modbus Auxiliary Map feature will allow you to configure data transfer to customize the mapping to meet specific application requirements.

As a Modbus TCP/IP Server all information from the PROFIBUS DP network is stored in continuous registers in the module for easy configuration and efficient mapping of data to a Modbus TCP/IP client.

Modbus Serial

On a Modbus Serial network the module will operate as either a Master or a Slave device supporting either RS232 or RS485 communication networks.

As a Modbus Serial Master the module can be configured to automatically read/write all PROFIBUS DP data with a slave device for easy setup and configuration, or the Modbus Auxiliary Map feature will allow you to configure data transfer to customize the mapping to meet specific application requirements.

As a Modbus Serial Slave all information from the PROFIBUS DP network is stored in continuous registers in the module for easy configuration and efficient mapping of data to an attached master device.

PROFIBUS DP Master V1

Cyclic or acyclic data can be transferred with Class 1 or Class 2 DPV1 services, allowing communication with slave devices supporting PROFIBUS DPV0 or V1 protocols. The gateway acts as an input/output link between the PROFIBUS network and the EtherNet/IP protocol. Data transfer by the EtherNet/IP protocol is asynchronous from data transfer on the PROFIBUS network.

  • Easy-to-use drag and drop configuration interface via ProSoft PLX50 Configuration Utility
  • GSD file import library
  • Monitoring and Modification of process data and DPV1 acyclic data
  • Multi-drop on a PROFIBUS DPV1 network with other compatible devices
  • Automatic project documentation, and Bus Parameter calculation
  • Supports online slave diagnostics, and extended diagnostic data (DPV1)
  • Auto baud detection at all valid PROFIBUS DPV1 rates up to 12 Mbps
  • Master Status LED Indicators for Operations, Network Communication, Master Token-Hold and Network Configuration.
  • Up to 125 Slaves can be connected with a repeater
  • Up to 1536 cyclic bytes input and 1536 bytes output data
  • Supports Extended Diagnostic Data
  • Alarm Handling (DPV1)
  • Supports Sync and Freeze commands
  • Supports PROFIdrive 3.1 compliant parameter read and write operations
    • Supports Multicast and Broadcast telegrams (DPV1)

 EtherNet/IP

 

Mode

Adapter

Connector

RJ45

Conductors

CAT5 STP/UTP

ARP Connections

Max 40

TCP Connections

Max 40

CIP Connections

Max 10

Communication Rate

10/100Mbps

Duplex Mode

Full / Half / Auto Negotiate

Auto MDIX

Yes

Modbus TCP/IP

Mode

Client or Server

Connector

RJ45

Conductors

CAT5 STP/UTP

ARP Connections

Max 40

Communication Rate

10/100Mbps

Duplex Mode

Full / Half / Auto Negotiate

Auto MDIX

Yes

Modbus Serial

Mode

Master or Slave

Media

RS232 or RS485

Baud Rate

1200, 2400, 4800, 9600, 19.2k, 38.4k, 57.6k, 115.2k

Data Bits

8

Stop Bits

1

Parity

None, Odd, Even

PROFIBUS DP

Protocol

PROFIBUS DP Master or Slave

Baud Rate

9600, 19.200, 45.5 kbps, 93.75 kbps, 187.5 kbps, 500 kbps, 1.5 Mbps, 3 Mbps, 6 Mbps, 12 Mbps

Support

DPV0 or DPV1

Cyclic I/O data

Input: 1536 bytes, Output: 1536 bytes

Stop bits

1

Untuk Permintaan Penawaran Harga & Stock Silahkan Hubungi Team'S Sales kami Dibawah ini :

Pemasaran :
1. Yadi.
Mobile : + 62-81297691617

Phone : 021 – 80808849 Ext.208

2. Ahmad Sudarman.

Mobile : + 62-81282819147

Phone : 021 – 80808849 Ext.209

PT. TOTAL ABADI SOLUSINDO

Authorized Distributor & Energy Management Contractor
Jl.Dr.Krt Radjiman Widyodiningrat Ruko D'Arcade Blok A19
D’Mansion Jatinegara Indah Central Bussiness Park, Pulo Jahe, Cakung , Jakarta Timur 13930
Phone   : +62-21-80808849 |Fax.  +62-21-80808848
Email   : info@totalabadisolusindo.co.id
Email   : sales@totalabadisolusindo.co.id
Web     : www.totalabadisolusindo.com

SUPPORT ALL BRAND & ALL MANUFACTURE :

|INVERTER|PLC|HMI|SOFT STARTER|AC SERVO|SENSOR & CONTROLLER|POWER SUPPLY|CIRCUIT BREAKER & CONNECTOR|TACHOMETER|FILTER|BATTERY CHARGER|
|ENCODER & COUNTER|SCALE & INDICATOR||FLOW METER|TESTER|WATER METER|SIGNAL LAMP|SAFETY RELAY|LOADCELL|FAN & BLOWER|INSTRUMENTS|GENSET|
|MODULE|VALVE|PUMP|PNEUMATIC & HYDRAULIC|PRESSURE TRANSMITTER|CLUTCH & BRAKE|ELECTRIC MOTOR|SHOCK ABSORBER|GRINDING WHELL|PANEL|PIPE|CABLE|
Tampilkan Lebih Banyak