| General specifications |
| Signal type | Digital Input |
| Functional safety related parameters |
| Safety Integrity Level (SIL) | SIL 2 |
| Supply |
| Connection | terminals 14, 15 |
| Rated voltage | 103.5 ... 126 V AC , 45 ... 65 Hz |
| Power dissipation | 1.2 W |
| Power consumption | max. 1.3 W |
| Input |
| Connection side | field side |
| Connection | terminals 1+, 2+, 3-; 4+, 5+, 6- |
| Rated values | acc. to EN 60947-5-6 (NAMUR) |
| Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
| Line fault detection | breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
| Pulse/Pause ratio | min. 20 ms / min. 20 ms |
| Output |
| Connection side | control side |
| Connection | output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12 |
| Output I, II | signal ; relay |
| Contact loading | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
| Mechanical life | 107 switching cycles |
| Transfer characteristics |
| Switching frequency | ≤ 10 Hz |
| Galvanic isolation |
| Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Indicators/settings |
| Display elements | LEDs |
| Control elements | DIP-switch |
| Configuration | via DIP switches |
| Labeling | space for labeling at the front |
| Directive conformity |
| Electromagnetic compatibility | |
| | Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Low voltage | |
| | Directive 2014/35/EU | EN 61010-1:2010 |
| Conformity |
| Electromagnetic compatibility | NE 21:2006 |
| Degree of protection | IEC 60529:2001 |
| Input | EN 60947-5-6:2000 |
| Ambient conditions |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Mechanical specifications |
| Degree of protection | IP20 |
| Connection | screw terminals |
| Mass | approx. 150 g |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Data for application in connection with hazardous areas |
| EU-Type Examination Certificate | PTB 00 ATEX 2081 |
| | Marking | II (1)G [Ex ia Ga] IIC
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I |
| | Input | Ex ia |
| | Voltage | 10.6 V |
| | Current | 19.1 mA |
| | Power | 51 mW (linear characteristic) |
| Supply | |
| | Maximum safe voltage | 126.5 V AC (Attention! Um is no rated voltage.) |
| Output | |
| | Contact loading | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load |
| | Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) |
| Galvanic isolation | |
| | Input/input | not available |
| | Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| | Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity | |
| | Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 |
| International approvals |
| FM approval | |
| | Control drawing | 116-0035 |
| UL approval | |
| | Control drawing | 116-0145 |
| CSA approval | |
| | Control drawing | 116-0047 |
| IECEx approval | IECEx PTB 11.0031 |
| | Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
| General information |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |