Contents | Specifications | |
---|---|---|
Input Voltage | AC85 - 264V 1Φ or DC120 - 350V * | |
Output | Wattage | 336W |
Voltage/Current | 24V 14A ACIN 100V 24V 14 (16.5) A ACIN 200V | |
Adjustable Voltage Range | 16.50 - 26.40V | |
Protection Circuit And Others | Overcurrent Protection | Works over 105% of rated current or 101% of peak current and recovers automatically |
Overvoltage Protection | 28.8 - 37.2V | |
Remote ON/OFF | Provided | |
Remote Sensing | Provided | |
Others | - | |
Operating Temperature/Humidity | -20 to +71℃ (Required Derating) , 20 - 90%RH (Non condensing) | |
Safety And Noise Regulations | Agency Approvals (At only AC input) | UL60950-1, C-UL (CSA60950-1) , EN50178, EN62368-1 Complies with DEN-AN |
Conducted Noise | Complies with FCC Part15 classB, VCCI-B, CISPR22-B, EN55011-B, EN55022-B | |
High Attenuation | Complies with IEC61000-3-2 * | |
Others | Dimensions (WxHxD) | 102x42x170mm [4.02x1.65x6.69 inches] (without terminal block and screw) |
Weight | 1.0kg max | |
Cooling Method | Forced cooling (internal fan) | |
Warranty Period | 5-year (Refer to Instruction Manuals) |